Calculator

Ventilation

Tunnel wind speed = total fan CFM ÷ house cross-section. Typical breeder target is about 2.0–2.5 m/s (400–500 ft/min) — set your own standard.

1. House & fan capacity

House dimensions in
House shape

What to measure

Gable-roof house: length, width, sidewall height and peak height measurements

Use the fan's rated CFM at the working static pressure (e.g. 0.10" water column), not free-air CFM. Target 2.50 m/s = 492 ft/min.

Expected wind speed

3.15 m/s

619 ft/min

Fans needed for 2.5 m/s

7

Installed fans are enough

Total fan capacity

200,000 CFM

Required 158,916 CFM

Air exchange

0.53 min

Time to replace all house air (aim ≤ 1 min in tunnel)

Cross-section

323 ft²

30.0 m²

House volume

105,944 ft³

3,000 m³

2. Actual reading vs standard

Wind speed in

Actual 1.80 m/s · 354 ft/min · Standard 2.50 m/s · 492 ft/min. Measure with an anemometer at bird level, in the middle of the house, averaging several points across the width.

Fans needed to reach standard

9

Turn on 3 more fans

Speed per fan

0.300 m/s

59.1 ft/min

Gap to standard

0.70 m/s

138 ft/min

Of standard

72%

Assumes each fan adds the same speed: 1.80 m/s ÷ 6 fans = 0.300 m/s per fan; 2.50 ÷ 0.300 = 8.33 → 9 fans. Low readings with all fans on point to dirty shutters, loose belts or air leaks.

3. Cooling pad area

19,988 CFM per fan.

Cooling pad area needed

39.7 m²

About 40 m² · 428 ft²

Total airflow

4,528 m³/min

159,905 CFM

Area per side

19.9 m²

2 sides

Pad length per side

9.9 m

at 2.0 m high

Pad area = (fan capacity × fans) ÷ air speed through pad: (566 × 8) ÷ 114 = 39.7 m².

Cobb standard wind speed by flock age

Recommended air speed at bird level (ventilation) based on age, for broilers and broiler breeders. Use this chart to set the target speed in section 1 and the standard speed in section 2 for the age of your flock.

Cobb standard wind speed guide: recommended air speed at bird level by age for broilers and broiler breeders